M9306-RDS6T
AI

## Electronic Specifications: M9306-RDS6T
The **M9306-RDS6T** is a high-performance, non-spring return electric actuator manufactured by Johnson Controls. It is primarily used to position dampers or valves in HVAC systems.
---
### 1. Key Electrical Specifications
The following table outlines the core electronic parameters required for installation and operation:
| Parameter | Specification |
| :--- | :--- |
| **Power Supply** | 24 VAC (nominal) at 50/60 Hz or 24 VDC |
| **Input Signal** | Floating (3-point) or On/Off |
| **Power Consumption** | 2.5 VA (Operating) / 1.1 W (Holding) |
| **Auxiliary Switches** | Two SPDT switches (rated 3A @ 24 VAC) |
| **Torque** | 53 lb·in (6 N·m) |
| **Runtime** | 60 Seconds for 90° rotation |
| **Electrical Connection** | 48 in. (1.2m) Halogen-free cable |
---
### 2. Control Logic & Feedback
The "RDS" designation indicates specific electronic features regarding control and feedback:
* **Floating Control:** The actuator uses two digital inputs. Powering one wire rotates the actuator clockwise; powering the other rotates it counter-clockwise. When neither is powered, the actuator remains in its last position.
* **Integrated Auxiliary Switches (-S models):** This unit includes two internal, field-adjustable switches. These provide electrical feedback to a controller or starter to confirm the damper's physical position (e.g., fully open or fully closed).
* **Microprocessor Control:** The internal circuitry uses a brushless DC motor controlled by a microprocessor to ensure constant torque and speed, regardless of load variations.
---
### 3. Wiring Configuration
Typical wiring for the M9306-RDS6T involves the following color-coded leads:
```text
Standard Control Wiring:
- Black (1): Common (24V ~ / -)
- Red (2): Power (24V ~ / +)
- White (3): Control Input (CW Rotation)
- Gray (4): Control Input (CCW Rotation)
Auxiliary Switch Wiring (Example):
- Yellow/Blue leads: Switch A (Common/NO/NC)
- Green/Red leads: Switch B (Common/NO/NC)
```
---
### 4. Electronic Protection Features
* **Overload Protection:** The actuator is electronically protected against stalling. It does not require limit switches; the microprocessor detects when the motor has reached its end-stop and cuts power to prevent burnout.
* **Enclosure Rating:** The electronics are housed in an **IP54 (NEMA 2)** rated enclosure, protecting against dust and light water splashing.
---
- ⤷
How do I adjust the internal auxiliary switches on the M9306-RDS6T?
- ⤷ Can this actuator be used with a 0-10V modulating signal?
- ⤷ What is the maximum damper area this actuator can drive?