METSECT5MB040
AI

The **METSECT5MB040** is a specific model of a Current Transformer (CT) from the Schneider Electric **PowerLogic** range. It is primarily used for energy metering and monitoring applications to scale down high currents to a level compatible with measurement devices.
---
### 1. Technical Specifications
The following table summarizes the core electronic and physical attributes of the METSECT5MB040:
| Feature | Specification |
| :--- | :--- |
| **Primary Current** | 400 A |
| **Secondary Current** | 5 A |
| **Accuracy Class** | Class 0.5 at 6 VA / Class 1 at 8 VA |
| **Type** | Tropicalized (for humid/harsh environments) |
| **Mounting Mode** | By screws or clip-on (DIN rail or plate) |
| **Busbar Dimensions** | 30 x 10 mm / 25 x 12.5 mm / 20 x 15 mm |
| **Insulation Voltage** | 720 V AC 50/60 Hz |
| **Compliance** | IEC 61869-2 & VDE 0414 |
---
### 2. Key Electronic Components & Design
The device functions based on the principle of **Electromagnetic Induction**. Its internal "parts" consist of:
* **Toroidal Magnetic Core:** A high-permeability steel core that concentrates the magnetic flux generated by the primary cable (the wire carrying the 400A).
* **Secondary Winding:** Multiple turns of copper wire wrapped around the core. This is where the secondary 5A current is induced.
* **Encapsulation (Casing):** Made of flame-retardant, UL94V-0 rated plastic. The "Tropicalized" designation means the internals are protected against high humidity and temperature fluctuations.
* **Terminals:** Secure screw-clamp terminals for connecting the 5A output to a power meter (such as a PowerLogic PM5000 series).
---
### 3. Application Use-Case
The METSECT5MB040 acts as the "sensor" for power management systems. It is typically installed in an electrical distribution board.
1. **Step-Down:** It transforms the 400A flowing through a main busbar down to 5A.
2. **Isolation:** It provides galvanic isolation between the high-power circuit and the sensitive electronic meter.
3. **Accuracy:** Being **Class 0.5**, it is precise enough for sub-billing and energy cost allocation.
---
### 4. Installation Diagram (Simplified)
```text
[ Main Power Cable (400A) ]
|
+-----|-----+
| [ CT ] | <-- METSECT5MB040
+-----|-----+
| (Secondary Output 5A)
+------> [ Power Meter / PLC ]
```
---
- ⤷
How do I determine the correct Accuracy Class for my metering application?
- ⤷ What is the maximum distance allowed between this CT and the meter?
- ⤷ Can this CT be used for protection relays or only for measurement?