11 / 20 page ![]() 3-3 MN1373 Figure 3-3 Current Signal Input Connection 4-20mA DC Signal Input: No resistor required. Set Jumper J1 in “CUR” position. 10-50mA DC Signal Input (Use Large Resistor with Color Code “Brown-Green-Brown”): Install the 150Ω - 1W resistor across Terminals “5” and “6”. Set Jumper J1 in“CUR” position. 1-5mA DC Signal Input (Use Small Resistor with Color Code “Brown-Black-Red”): Install the 1kΩ - 1/4W resistor across Terminals “5” and “6”. Set Jumper J1 in “VOLT” position. Procedure to Calibrate the Signal Isolator When Using Current Signal Input: 1. Connect a DC voltmeter (a digital voltmeter is suggested) to Terminals “9” (-) and“10” (+). 2. Apply the minimum signal input current to Terminals “5” (-) and “6” (+). 3. Adjust the MIN Trimpot on the Signal Isolator to obtain an output voltage of 0VDC. 4. Apply the maximum signal input current to Terminals “5” (-) and “6” (+). 5. Adjust the MAX Trimpot on the Signal Isolator to obtain an output voltage of 9VDC. |
|
|
Link URL |
| War ALLDATASHEET hilfreich? [ DONATE ] |
Über Alldatasheet | Werbung | Kontakt | Privatsphäre und Datenschutz | Link zum Datenblatt | Linktausch | Hersteller All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|