  CP2000AC54PE Datasheet HTML 1Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 2Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 3Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 4Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 5Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 6Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 7Page - Lineage Power Corporation CP2000AC54PE Datasheet HTML 8Page - Lineage Power Corporation  
Zoom Inzoom in Zoom Outzoom out
 5 / 8 page
background image
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Lineage Power
5
Status and Control
The rectifier provides three means for
monitor/control: analog, PMBus compliant I
2C, or
RS485 for interfacing to Lineage Power controllers
or battery plants.
Details of analog controls are provided in this data
sheet under Signal Definitions. Lineage Power will
provide separate application notes on PMBus
protocol for users to interface to the CPL rectifiers.
Contact your local Lineage Power representative
for details.
Hot Plug
When rapidly extracting and reinserting modules
care should be taken to allow for discharging the
internal bias supply so that a predictable restart
could be achieved. The way to ensure that the
circuit sufficiently discharges is to observe the
spinning of the fans after an extraction. The unit
should not be reinserted until the fans stop
spinning.
Control Definitions
All signals are referenced to Logic GRD unless
otherwise noted. See the Signal Definitions Table
at the end of this document for further description
of all the signals.
Input Signals
Margining:
Setpoint of the rectifier can be changed
via this input pin. Programming can be either a
voltage source or a resistance divider. The
margining pin is connected to 3.3Vdc via a 10kΩ
resistor inside the rectifier. See graphs below.
An open circuit on this pin reverts the voltage level
back to the original setting.
Module Present Signal:
This signal has dual
functionality. It can be used to alert the system
when a module is inserted. Has a 500
Ω resistor in
series between this signal and Logic GRD. An
external pull-up should not raise the voltage on the
pin above 0.25Vdc. If raised the pin is raised to
5Vdc the write_protect feature of the EEPROM is
enabled.
Protocol Select:
Establishes the communications
mode of the power supply, between analog/I
2C and
RS485 modes. For RS485, connect 750 – 3.92kΩ
pull-down resistor to 54_OUT(-DC).
Enable:
On/Off control when either PMBus
communications or analog functions are utilized as
configured by the Protocol pin. This pin must be
pulled low to turn ON the main output of the power
supply. The power supply will turn OFF if either the
Enable
or the ON/OFF pin is released. The Enable
function does not work with the RS-485 protocol.
This signal is referenced to Logic_GRD.
ON/OFF:
This is a short pin utilized for hot-plug
applications to ensure that the power supply turns
OFF
before the power pins are disengaged. It also
ensures that the power supply turns ON only after
the power pins have been engaged. Must be
connected to 54_OUT (-DC).
Output Signals
Alert #:
PMBus interrupt signal.
Fault:
This signal goes LO for any failure that
requires rectifier replacement. Some of these faults
may be due to:
Fan failure
Over-temperature condition
Over-temperature shutdown
Over-voltage shutdown
Internal Rectifier Fault
Power Capacity:
A HI on this pin indicates rectifier
configured for 2000W operation; a LO indicates
rectifier configured for 1200W operation.



Html Pages

1 2 3 4 5 6 7 8


Datenblatt Download

Go To PDF Page


Link URL



War ALLDATASHEET hilfreich?  [ DONATE ] 

Über Alldatasheet   |   Werbung   |   Kontakt   |   Privatsphäre und Datenschutz   |   Link zum Datenblatt    |   Linktausch   |   Hersteller
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com