21 / 26 page ![]() CP10.121 CP-Series 12V, 16A, SINGLE PHASE INPUT 24. APPLICATION NOTES 24.1. PEAK CURRENT CAPABILITY The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when starting a capacitive load. The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. In case of a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of over-current to open in a timely manner. This avoids voltage loss in adjacent circuits. The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following two examples show typical voltage dips: Fig. 24-1 Peak load with 2x the nominal current for 50ms, typ. Fig. 24-2 Peak load with 5x the nominal current for 5ms, typ. 10ms/DIV Output Voltage Output Current 12V 0A 32A 8.6V 1ms/DIV Output Voltage Output Current 12V 0A 80A 7.1V 32A Peak load (resistive) for 50ms Output voltage dips from 12V to 8.6V. 80A Peak load (resistive) for 5ms Output voltage dips from 12V to 7.1V. Fig. 24-3 48A Peak load, typ. 10ms/DIV Output Voltage Output Current 0A 12ms 48A 12V 5.8V Please note: The DC-OK relay triggers when the voltage dips more than 10% for longer than 1ms. High Overload Current (typ. 48A for 12ms) enables easy fuse tripping Peak current voltage dips typ. from 12V to 8.6V at 32A for 50ms, resistive load typ. from 12V to 7.4V at 80A for 2ms, resistive load typ. from 12V to 7.1V at 80A for 5ms, resistive load Feb. 2016 / Rev. 1.1 DS-CP10.121-EN All parameters are specified at 12V, 16A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 21/26 |
|
|
Link URL |
| War ALLDATASHEET hilfreich? [ DONATE ] |
Über Alldatasheet | Werbung | Kontakt | Privatsphäre und Datenschutz | Link zum Datenblatt | Linktausch | Hersteller All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |